Grundfos UPE Series - Start-Up; Venting the Pump

Grundfos UPE Series
315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
10
Note:
All cables used must be heat-resistant up to
at least +85 °C.
All cables used must be installed in accordance
with EN 60204-1.
Concerning demands on signal wires and signal
transmitters, see section 12. Technical data.
6. Start-up
Do not start the pump until the system has been filled
with liquid and vented. Furthermore, the required
minimum inlet pressure must be available at the
pump inlet. See section 12. Technical data.
6.1 Venting the pump
Vent the pump before start-up. See fig. 7.
Fig. 7 Venting the pump
The pump may be noisy, when first switched on,
due to air remaining in the pump. This noise should
cease after a few minutes running.
After start-up, set the desired operating mode and
possibly pump head.
19 Control panel retaining screws
20 Terminal for fan
21 High-voltage indicator
22 Terminal for screened motor cable
23 Fan
Warning
Wires connected to
outputs 7 and 8,
inputs 1 to 6,
supply terminals and
differential-pressure and
temperature sensor
must be separated from each other and
from the supply by reinforced
insulation.
All wires connected to a terminal block
must be tied up at the terminals.
Note
The system cannot be vented through
the pump.
Warning
When the vent screw is slackened,
scalding hot liquid under high pressure
may escape. Care must be taken to
ensure that the escaping liquid does
not cause personal injury or damage to
other components.
TM04 4635 1809 - TM04 4636 1809
Vent screw