EasyManua.ls Logo

Grundfos UPE Series - Wiring Diagram

Grundfos UPE Series
315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
9
5.2 Wiring diagram
Fig. 6 Internal view of the control box
TM04 4634 4709
Pos. Description
A, Y, B Terminal block for GENIbus
T Terminal block for twin-head pump
D Terminal block for pressure and temperature sensor on the pump (standard)
1, 2 (START/STOP)
Terminals for external start/stop
(connect only contacts with no voltage)
3, 4 (MIN.)
Terminals for min. curve input
(connect only contacts with no voltage)
5, 6 (0-10 V)
Terminals for external analog input 0-10 VDC
Terminal 5 = +10 V
Terminal 6 = 0 V
7, 8 (ALARM) Terminal block for remote alarm contact. Maximum load: 250 VAC, 5 A.
9, 10, 11
Terminals for supply voltage, 1 x 230 V, 50-60 Hz
Terminal 9 = Line (L)
Terminal 10 = Earth ( )
Terminal 11 = Neutral (N)
12, 13, 14
Terminals for connection of motor cables
Terminal 12 = brown lead
Terminal 13 = grey lead
Terminal 14 = black lead
15 Motor earthing screw
16, 17 Terminals for connection of motor protector, white lead (T1, T2)
18 Terminal for control panel

Table of Contents