C-9105R
Conventional Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
8
Detector
Reflector
7m
6m
Fig. 5
c) When space height is more than 8m, the roof is normally
gabled without ceiling, the detector and reflector should be
mounted on the two facing walls about 8m from the floor,
ensuring that the vertical distance between the
detector/reflector and top of the building is more than 0.5m,
refer to Fig. 6. The distance should be 7m from the detector
to the floor.