C-9105R
Conventional Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
2
convenient to operate.
(5) Self-diagnosis function can monitor the inner fault.
(6) Automatic compensation for factors weakening received signals,
such as dust contamination, positional excursion and ageing
transmitter.
(7) It has volt-free output contacts for fire alarm and fault.
(8) Two sensitivity levels can be set in field.
(9) The detector’s optical pathway is designed with strong
anti-interference ability.
(10) SMT processing technology.
(11) Attractive and decent appearance.
III Technical Specification
(1) Power Voltage: 15VDC28VDC
(2) Power Current: Commission current20mA
Standby current12mA
Alarm current22mA
(3) Fire Alarm and Fault Contact Output:
Fire Alarm Relay: Contact capacity 28V/2A, which is normally
open in normal state and closed in fire alarm state.
Fault Relay: Contact capacity 28V/2A, which is normally closed
in normal state and open in fault state.
(4) Angle of Adjusting: -6°+6°
(5) Maximum angular misalignment: ±0.5°
(6) Sensitivity Level:
Level 1: High sensitivity.
Level 2: Low sensitivity.
(7) Indication of Detector State:
Commission: Green LED and Yellow LED are lit or flash in a
HTTP://GSTRU.RUE-MAIL: hombi@hombi.ru