– 51 –
Compressor
Wiring: Compressor Check
CAUTION: Risk of injury. Keep head clear of
terminal area when cover is removed.
Keep head clear of terminal area when cover is
removed.
Check windings rst. If open or grounded, DO
NOT apply power to compressor terminals.
Reversing Valve
*Shown with solenoid removed.
Reversing Valve Solenoid Coil
BTU/Size V Run Start
7K/230V 5.139±7% Ω 6.032±7% Ω
7K/265V 6.747±7% Ω 4.680±7% Ω
9K/230V 3.319±7% Ω 2.635±7% Ω
9K/265V 4.503±7% Ω 3.298±7% Ω
12K/230V 2.526±7% Ω 2.313±7% Ω
12K/265V 3.296±7% Ω 2.505±7% Ω
15K/230V 2.227±7% Ω 3.093±7% Ω
15K/265V 2.840±7% Ω 3.225±7% Ω
Compressor Resistance
Resistance spec is reported as room temperature
readings.
BTU Microfarads
7k 15 uF +/- 5%
9k 30 uF +/- 5%
12k and 15k 30 uF +/- 5%
Capacitor Microfarads
On heat-pump models, the refrigerant ow
direction is controlled by the reversing valve
assembly. In the cooling mode, the main board
supplies line voltage to the solenoid coil, which
causes the valve to switch ow direction. With no
voltage applied to the solenoid coil, the valve will
be in the heating mode.
The solenoid coil attaches to the valve body with
a 5/16-in. hex-head bolt. The 230/208-volt coil
has pink wires and measures approximately 1.5k
ohms.