– 9 –
For both AZ4500 and AZ6500, once the 
compressor comes on in cooling, it will pull the 
room temperature down to the thermostat setting.
Fan pulsing for temperature checking after 
compressor shut-off, when not in Class 2 
mode: 
•  The Zoneline will pulse the indoor fan 
periodically when it is not on a remote 
thermostat and set to cycle cooling.
•  The system will wait 6 minutes after the 
compressor shuts off, then pulse the indoor 
fan, pulling air across the air sensor for a 
duration of 30 seconds.
•  Should the rst 2 minute pulse not activate 
the Zoneline, the system will continue pulsing 
until cooling is needed.
•  Each pulse of the fan is running at low speed, 
no matter what setting the user has chosen.
Operation
  Cooling
AZ4500 In the cooling mode, the 
compressor, indoor fan and outdoor 
fan run.
AZ6500 In the cooling mode, the 
compressor, indoor fan and outdoor 
fan run, the reversing valve is 
energized throughout the entire 
cooling cycle.
  Heating
AZ4500 In the heating mode, AZ4500 will 
utilize the built-in resistance heater, 
running with the indoor fan at one of 
two speeds determined by the Fan 
Speed selection.
Resistance heater output is not determined by 
software.  It is determined by hardware (power 
cord amperage rating).
Temperature control in the heating mode is done 
by cycling the resistance heater under control of 
the room air sensor, or the room thermostat (if in 
Class 2 Mode).
Whenever the room temperature is 1.8°F below 
the temperature setting, the control will energize 
the heating cycle and remain in operation until 
the room temperature reaches the temperature 
setting.  At this point, the Zoneline will turn off the 
heating cycle.
Room  Temp       
Setpoint 1.8°F
Room Temp
ON
ON
Room  Temp        
Setpoint
Room Temp 
Setpoint        
1.8°F
ON ON
Heating 
Mode