– 12 –
 All Heat Pump Lockout Mode
AZ6500 Series ONLY.
The Heat Pump Lockout is controlled through 
the Auxiliary Set mode.  When this Auxiliary 
Set button is on, the control will run in electric 
resistance heat (Stage 3) mode only, with the 
heat pump operation (Stage 1 and 2 heating) off. 
When the Auxiliary Set button mode is off, the 
heat pump is allowed.
The heat pump lockout mode is utilized in the 
Class 2 mode.
NOTE: If the Heat Pump Lockout mode and 
Boost Heat mode are both selected as active in 
the auxiliary settings, the Heat Pump Lockout 
mode takes priority, and Heat Pump modes 
remain off.
  Boost Heat Mode
AZ6500 Series ONLY.
When the Boost Heat Auxiliary Set button is 
enabled and the outdoor temperature is above 
25°F, the rst stage heat (heat pump only) is 
locked out.
It will be controlled through an Auxiliary Set 
Button mode.  Staged Heating selection logic and 
Resistance Heat Lockout mode have priority over 
this function.
This Boost Heat setting is used to provide 
supplementary heat to the heat pump operation 
in conditions where the heat pump only operation 
(Stage 1 heat) is not sufcient to maintain a 
consistent comfortable room temperature for the 
consumer. 
Fan Only Mode: All models
In the Fan Only mode, the indoor fan runs 
continuously at the fan speed selected (High or 
Low).  All other loads are de-energized.