– 52 –
NOTE: Reversing valve assemblies will come 
complete with tubing, so excess heat will not be 
applied to the valve body.
Tank
On 7k and 9k heat-pump models, a receiver tank 
is included in the sealed system.  This tank is 
soldered to the outdoor coil return line tube.
Check Valve
This valve allows the ow of refrigerant one way 
unimpeded, but in heat pump mode it closes and 
forces the refrigerant to go through an additional 
length of capillary tube.  This helps balance the 
refrigerant system.
NOTE: Care must be taken when soldering 
in the new check valve.  Thermal paste and a 
damp rag must be used on the middle portion of 
the assembly to prevent thermal damage to the 
internal check ball assembly.
Drier
All Zonelines will now have a drier factory 
installed.  The drier must be replaced anytime 
sealed system repairs are performed. 
NOTE: Driers are vacuumed packed and should 
only be opened when it is being installed.  Driers 
opened and left to the open air become saturated 
and should be discarded if not used within 45 
minutes.
  Service Replacement Valve Assembly
Heat pump drier kit shown: Includes the check 
valve, drier, capillary jumper and process stub