EasyManua.ls Logo

Haier MRV5-H - Page 129

Haier MRV5-H
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
Failure code
Outdoor
digital
display tube:
112- 4, 5
Indoor wired
controller:
70
Indoor unit LED status
LED5 Failure description:
Fan motor module radiator temp. too high
20 times
Outdoor unit LED status
LED1 LED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series
DiagnosisT roubleshooting
2. Abnormity detection method
Check if the radiating of the
fan motor aluminum radiator is
good
Check if the fan is good
conditions
Motor built-in IGBT bottom
radiator temperature reaches
95.65 degree;
4. Possible causes
Motor built-in IGBT radiating
poor;
Outdoor fan does not turn or
stuck
Check if outdoor fan can rotate
Check i f the fan rotation i s
smooth
When 112 fault occurs,
whether the motor at high
speed
The motor is overloaded
and check the reason
Check the fan blocked reason
Replace fan motor
Check whether t he o utdoo r
fan stuck, d amaged, adjust t he
replace fan
Y
Y
Y
N
N
N

Table of Contents