165
PART 2 Enginnering Data
12. Specications
230V VRF Outdoor Unit
Items New Heat Pump
Heat Recovery
Marketing Model Name MVHQ072ME2CA MVHQ096ME2CA MVHQ120ME2CA
Model Name
System 6T 8T 10T
Combination / / /
Brand Haier Haier Haier
Norminal Capacity (Btu/h) 72000 96000 120000
Factory Model Number AV08CMVURAB AV10CMVURAB AV12CMVURAB
Electrical
Voltage, Cycle, Phase V/Hz/- 208-230/60/3 208-230/60/3 208-230/60/3
Maximum Fuse Size A 40 50 60
Minimum Circuit Amp A 30 38 41
Performance
Non-Ducted
Rated Cooling Capacity@95°F (Btu/h) 69000 91000 115000
EER @95 °F 12.6 11.9 11.6
IEER 23.6 23.1 23
Rated Heating Capacity @47°F(Btu/h) 77000 103000 129000
COP @ 47°F 3.5 3.5 3.5
Rated Heating Capacity@17°F(Btu/h) 53000 72000 84000
COP @ 17°F 2.4 2.4 2.5
SCHE 24.4 23 21.7
(115°F) Cooling Capacity(Btu/h) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @5° (-15C) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @-4°F (-20C) ≥70% of rated ≥70% of rated ≥70% of rated
Heating Capacity @-13°F (-25C) ≥60% of rated ≥60% of rated ≥60% of rated
Heating capacity @-22°F (-30C) ≥25% of rated ≥25% of rated ≥25% of rated
Performance
Ducted
Rated Cooling Capacity@95°F (Btu/h) 69000 91000 115000
EER @95 °F 12 12.2 11.2
IEER 20.5 21.8 21.6
Rated Heating Capacity @47°F(Btu/h) 77000 103000 129000
COP @ 47°F 3.5 3.5 3.5
Rated Heating Capacity@17°F(Btu/h) 53000 72000 84000
COP @ 17°F 2.4 2.4 2.5
SCHE
20
21.4 21.4
(115°F) Cooling Capacity(Btu/h) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @5°F ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @-4°F ≥70% of rated ≥70% of rated ≥70% of rated
Heating Capacity @-13°F ≥60% of rated ≥60% of rated ≥60% of rated
Heating capacity @-22°F (-30C) ≥25% of rated ≥25% of rated ≥25% of rated

Table of Contents

Related product manuals