EasyManua.ls Logo

Haier MRV5-H - Configuration Dip Switches

Haier MRV5-H
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
5. Indoor unit
--Anti-dust protection during installation
--Installed proper and level
--Service space reserved at least 19.69X19.69 inch
6. Outdoor unit
-- Installed on anti-vibration pads at bottom
-- Space (20cm/7.87inch away from each other)
-- Gather ttings are the same level
-- Breaker
-- Communication cable (A / B / C, PQ)
7. Pre start up
-- 100% of the piping completed and pressure test passed
-- Vacuum test
-- The system has been with electric power more than 6 hours
-- Outdoor unit addressing (Master 0, slave1, slave2)
-- Indoor units are addressed correctly
-- All the indoor units work correctly in Fan mode
6.1.3 Conguration Dip Switches
1. Indoor dip switch setting—Indoor units for MRV5 and indoor units for MRV IV-C are the same, so indoor dip
switch setting is the same; please check with the service manual.
2. Controller dip switch setting- it’s the same as the controller dip switch setting of MRV-IV, please check the
service manual.
IDU Dip switch setting
For di󰀨erent IDU PCB board; the setting is little di󰀨erent. When start up, check the Dip switch settings below:
SW01 (1~4 or 2~4)--------Set the master/slave unit when wired controllers are in group control
SW01 (5~8)-----------------Set the capacity of the unit (default setting, no need to reset)
SW03 (1~8)------------------Set the communication address and central address (the default setting is set the address
by wired controller or automatically)
ODU Dip switch setting
The engineer set on site
Pre-set in factory
Check operating parameter & E2
control
Dip switch
BM-1
BM-2
BM-3
BM-4
SW1
SW2
SW3

Table of Contents

Related product manuals