79
Startup control on indoor and outdoor units and operation condition inspection for outdoor units can be completed
through rated operation. In case of inspection on single indoor unit, wired controller or remote controller of indoor
unit will be adopted for control.
Rated cooling operation: when SW1, SW2 and SW3 dip switches are turned to 0, 13, 2, the indoor units will be
started up automatically and be forced to turn to cooling operation.
Rated heating operation: when SW1, SW2 and SW3 dip switches are turned to 0, 14, 2, the indoor units will be
started up automatically and be forced to turn to heating operation.
The test run conrmation, in principle, shows that all the indoor units should be conrmed one by one. Improper
connection of refrigeration lines and control wires cannot be conrmed when all the indoor units are running
simultaneously so all the other indoor units should be set in "stopped condition".
7.2.2 Rated Operation
7.2.3 Trial Operation Conrmation
A. Main power supply and initial conrmation
*3
*2
*1
Whether the operation light of wired controller is on
Whether the LCD "standby" of wired controller is
turned on
Whether the overhaul code of wired controller is
displayed
Please refer to maintenance code displayed of wired
controller and fault identification
method. For detailed
confirmation of operation condition, please refer to
self-diagnosing function of outdoor unit.
No
No
Yes
Yes
Yes