130
Failure code
Outdoor
digital
display tube:
117-0, 1
Indoor wired
controller:
75
Indoor unit LED status
LED5 Failure description:
Compressor module software over current
20 times
Outdoor unit LED status
LED1 LED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series
DiagnosisT roubleshooting
2. Abnormity detection method
Check if the compressor is
insecurely connected;
Check the system for liquid
shock.
Check if the module is in
normal conditions and subject
to short circuit.
Check if the compressor is
well.
Check if the compressor
wiring UVW is connected
correctly and the inverter board
and module board is securely
wired.
conditions
Over current of module software
4. Possible causes
The current detection
loop of inverter board is in
poor performance, which
results in rapid current rise of
compressor;
Damage or liquid shock is
found in compressor, which
results in over current;
UVW wiring is wrongly
connected or the inverter board
and module board are wired
insecurely.
Check if the supply voltage is normal.
Check if the electrical
cabinet is wired correctly,
the compressor matches
U, V and W correctly
and the variable frequency
board and module board
is connected securely.
Check if the power module is normal.
Check i f the detection circuit of
variable frequency board is normal.
Check if the winding and insulation
of compressor is normal.
Replace and c ompare th e
neighboring electrical cabinet
by exclusion method
accordance with the circuit diagram.
Adjust the supply voltage.
Replace the power module.
Replace the variable frequency
board.
Replace the compressor.
Y
Y
Y
Y
Y
N
N
N
N
N

Table of Contents