139
Failure code
Outdoor
digital
display tube:
125-0, 1
Indoor wired
controller:
7D
Indoor unit LED status
LED5 Failure description:
Compressor frequency un-match
20 times
Outdoor unit LED status
LED1 LED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series
Diagnosis Troubleshooting
2. Abnormity detection method
Check if the communication
circuits of power module and
inverter board are securely
inserted and connected.
Check if the power module
is well.
Check if the inverter board
is well.
conditions
target frequency +3Hz) or
frequency =0) for continuous 5
minutes
4. Possible causes
The power module and
inverter board are connected
loosely, which results in
detection failure of compressor
rotation speed.
The power module is
damaged.
Y
Whether the power supply voltage is
N
Adjust the power supply.
Y
Check if the electrical box connect
correctly
Reconnect o r re-fix i t in
accordance w ith w irin g
diagram.
N
C heck i f the inverter m odule is
normal
N
Replace the inverter module
Y
Compressor winding resistance ,
insulation is normal
N
Replace the compressor