B. Compressor Replacement – double compressors unit
Step 1. Remove the front panel and release the refrigerant from the system through the stop valve.
Step 2. Remove the compressor cushion from the compressor and then remove the power wire and ground wire.
Step 3. Remove four anchor bolts of the compressor.
compressor
cushion
anchor bolts
power wire and
ground wire