167
Items New Heat Pump
Heat Recovery
Marketing Model Name MVHQ144ME2CA MVHQ168ME2CA MVHQ192ME2CA
Model Name
System 12T 14T 16T
Combination / / /
Brand Haier Haier Haier
Norminal Capacity (Btu/h) 144000 168,000 192,000
Factory Model Number AV14CMVURAB AV16CMVURAB AV18CMVURAB
Electrical
Voltage, Cycle, Phase V/Hz/- 208-230/60/3 208-230/60/3 208-230/60/3
Maximum Fuse Size A 80 90 110
Minimum Circuit Amp A 56 59 71
Performance
Non-Ducted
Rated Cooling Capacity@95°F(Btu/h) 138000 160000 184000
EER @95 °F 10.8 11.4 11.2
IEER 20 23.2 22.2
Rated Heating Capacity@47°F(Btu/h) 154000 180000 206000
COP @ 47°F 3.4 3.6 3.5
Rated Heating Capacity@17°F(Btu/h) 108000 122000 138000
COP @ 17°F 2.4 2.5 2.4
SCHE 21.6 26 26.7
(115°F) Cooling Capacity (Btu/h) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @5° (-15C) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @-4°F (-20C) ≥70% of rated ≥70% of rated ≥70% of rated
Heating Capacity @-13°F (-25C) ≥60% of rated ≥60% of rated ≥60% of rated
Heating Capacity @-22°F (-30C) ≥25% of rated ≥25% of rated ≥25% of rated
Performance
Ducted
Rated Cooling Capacity@95°F (Btu/h) 138000 160000 184000
EER @95 °F 10.8 11.5 11.3
IEER 20.3 21.5 21.1
Rated Heating Capacity @47°F(Btu/h) 154000 180000 206000
COP @ 47°F 3.4 3.4 3.3
Rated Heating Capacity@17°F(Btu/h) 108000 122000 138000
COP @ 17°F 2.4 2.4 2.4
SCHE 20.6 24.7 24.4
(115°F) Cooling capacity(Btu/h) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @5°F ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @-4°F ≥70% of rated ≥70% of rated ≥70% of rated
Heating Capacity @-13°F ≥60% of rated ≥60% of rated ≥60% of rated
Heating Capacity @-22°F (-30C) ≥25% of rated ≥25% of rated ≥25% of rated