169
Items New Heat Pump
&
Heat Recovery
Marketing Model Name MVHQ216ME2CA MVHQ240ME2CA MVHQ264ME2CA
Model Name
System 18T 20T 22T
Combination / / 10T+12T
Brand Haier Haier Haier
Norminal Capacity (Btu/h) 216,000 240,000 264000
Factory Model Number AV20CMVURAB AV22CMVURAB /
Electrical
Voltage, Cycle, Phase V/Hz/- 208-230/60/3 208-230/60/3 208-230/60/3
Maximum Fuse Size A 125 135 60+80
Minimum Circuit Amp A 83 87 41+56
Performance
Non-Ducted
Rated Cooling Capacity@95°F(Btu/h) 206000 222000 253000
EER @95 °F 10.9 10.1 10.1
IEER 22 20.3 18.8
Rated Heating Capacity@47°F(Btu/h) 232000 240000 282000
COP @ 47°F 3.5 3.4 3.3
Rated Heating Capacity@17°F(Btu/h) 156000 168000 192000
COP @ 17°F 2.4 2.4 2.3
SCHE 25.6 24.6 25.2
(115°F) Cooling Capacity (Btu/h) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @5° (-15C) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @-4°F (-20C) ≥70% of rated ≥70% of rated ≥70% of rated
Heating Capacity @-13°F (-25C) ≥60% of rated ≥60% of rated ≥60% of rated
Heating Capacity @-22°F (-30C) ≥25% of rated ≥25% of rated ≥25% of rated
Performance
Ducted
Rated Cooling Capacity@95°F (Btu/h) 206000 222000 253000
EER @95 °F 11.3 10.6 9.8
IEER 20.8 20.3 19.4
Rated Heating Capacity @47°F(Btu/h) 232000 240000 282000
COP @ 47°F 3.3 3.3 3.3
Rated Heating Capacity@17°F(Btu/h) 156000 168000 192000
COP @ 17°F 2.4 2.3 2.3
SCHE 24.2 23.6 23.3
(115°F) Cooling capacity(Btu/h) ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @5°F ≥80% of rated ≥80% of rated ≥80% of rated
Heating Capacity @-4°F ≥70% of rated ≥70% of rated ≥70% of rated
Heating Capacity @-13°F ≥60% of rated ≥60% of rated ≥60% of rated
Heating Capacity @-22°F (-30C) ≥25% of rated ≥25% of rated ≥25% of rated