187
Items New Heat Pump
Heat Recovery
Marketing Model Name MVHQ432ME4CA MVHQ456ME4CA
Model Name
System 36T 38T
Combination 18T+18T 10T+14T+14T
Brand Haier Haier
Norminal Capacity (Btu/h) 432000 456000
Factory Model Number / /
Electrical
Voltage, Cycle, Phase V/Hz/- 460V/60/3 460V/60/3
Maximum Fuse Size A 70+70 30+60+60
Minimum Circuit Amp A 47+47 22+40+40
Performance
Non-Ducted
Rated Cooling Capacity@95°F(Btu/h) 400000 436000
EER @95 °F 8.9 9
IEER 17.5
16.2
Rated Heating Capacity@47°F(Btu/h) 410000 476000
COP @ 47°F 3.2 3.2
Rated Heating Capacity@17°F(Btu/h) 300000 342000
COP @ 17°F 2.15 2.15
SCHE 17.9 15.6
(115°F) Cooling Capacity (Btu/h) ≥80% of rated ≥80% of rated
Heating Capacity @5° (-15C) ≥80% of rated ≥80% of rated
Heating Capacity @-4°F (-20C) ≥70% of rated ≥70% of rated
Heating Capacity @-13°F (-25C) ≥60% of rated ≥60% of rated
Heating capacity @-22°F (-30C) ≥25% of rated ≥25% of rated
Performance
Ducted
Rated Cooling Capacity@95°F (Btu/h) 400000 436000
EER @95 °F 9 9
IEER 18.1 17.1
Rated Heating Capacity @47°F(Btu/h) 410000 476000
COP @ 47°F 3.2 3.2
Rated Heating Capacity@17°F(Btu/h) 300000 342000
COP @ 17°F 2.2 2.2
SCHE 17.6 19.1
(115°F) Cooling Capacity(Btu/h) ≥80% of rated ≥80% of rated
Heating Capacity @5°F ≥80% of rated ≥80% of rated
Heating Capacity @-4°F ≥70% of rated ≥70% of rated
Heating Capacity @-13°F ≥60% of rated ≥60% of rated
Heating Capacity @-22°F (-30C) ≥25% of rated ≥25% of rated

Table of Contents