257
The wiring for the power line and signal line of valve box
Graphical representation for wiring
The wiring for the power line of valve box, the wiring for the signal line between valve boxes and outdoor units as 
well as the wiring between valve boxes. 
Items
Total       
Current 
of valve 
boxes (A)
Cross 
Section
(mm
2
)
Rated 
Current of 
Overow 
Breaker (A)
Rated Current of Power Leakage 
Breaker (A)
Leaking Current (mA)
Operating Period (S)
Cross Sectional Area of Signal Line
Outdoor-valve 
box (mm
2
)
Valve box-valve 
box (mm
2
)
<15 6(2.5) 15 15A, 30mA, 0.1S or below 2cores ×0.75-2.0 mm
2
 shielded line
•  Power cable and communication wire must be xed rmly.
•  Each valve box must be earthed well.
•  When power cable exceeds the range, thicken it appropriately.
•  Shielded layer of communication wires must be connected together and be earthed at single 
point.
•  Communication wire total length cannot exceed 1000m.
Connect the communication terminal block P and Q of the main unit of the outdoor units with the communication 
terminal block P and Q of the rst valve box (VP 1).
P
Q
B
C
L
N
L
N
P
Q
A
B
C
A
B
C
C1
C2
P1Q1
P
2Q2P3Q 3P4Q4
PQ
AB
C
AB
C
PQ
A
B
C
AB
C
PQ AB C
A
B
C
PQ AB C
A
B
C
L
N
PQ AB C
PQ
A
B
C
Indoor 9
AB
C
wired 
controller
wired 
controller
A
B
C
Outdoor 1
Indoor 1
wired 
controller
wired 
controller
Indoor 2
VP 1
P Q A BC
Outdoor 2 Outdoor 3
VP4-560B
VP 3
Indoor 1-4
Indoor 8
To power supply
1PH,220-230V~,
50/60Hz
Rated Current 
of Overow 
Breaker
Outdoor Indoor
communication wire with polarity
The communication wire of valve boxes and 
outdoor units as well as between valve boxes with 
non-polar. 
Cooling and Heating are Optional Indoors
Just Cooling Indoors
A B C
A B C
B
P Q A BC PQA BC
A BC
ABC
Outdoor
Outdoor Indoor
P Q B C
Indoor 4
Indoor 3 Indoor 6
Indoor 5
wired 
controller
wired 
controller
wired 
controller
wired 
controller
Indoor 7
wired 
controller
Notes:
(1) The above wiring example is only for reference. The number of valve boxs and indoor units 
shall be subject to the eld installation.
(2) Communication line from cooling-only indoor unit may be connected to the communication 
terminal block P and Q (outdoor) of the valve box.