45
MRV 5-H
ENGLISH BETA 1.2
SYSTEM START UP LIST
SYSTEM CODE MODEL
* Refrigerant recharge calculation
Liquid pipe size  Multiple factor Length Subtotal
1/4" (6.35) 0.022
3/8" (9.52) 0.054
1/2" (12.7) 0.11
3/4" (15.88) 0.17
5/8" (19.05) 0.25
7/8" (22.22) 0.35
1" (25.4) 0.52
Total(lb)
Outdoor unit No. Model Serial No.
Master
Slave1
Slave2
*Please input measured voltage values before start up: 
L1 vs. L2 V L1 vs. N V L1 vs. Ground V
L2 vs. L3 V L2 vs. N V L2 vs. Ground V
L3 vs. L1 V L3 vs. N V L3 vs. Ground V