6.4.10 Coil Protection Control
By controlling the frequency of the compressor to control the temperature of the coil, and the coil temperature is
usually controlled at 203°F. Above 203°F, the outdoor fan increases the speed.
6.4.11 Anti-Snow Protection
6.4.12 Heater Control
When the system is running, control the heater according to the following picture.
When the compressor oil temperature Toil is 140-149°F, it starts from ON.
CH: Heater (Crank Case Heater)
6.4.13 Target Pressure Control
Cooling low pressure control
Target Pressure Ps When Cooling Remarks
Long piping setting 14.3 lb
Medium piping setting 16.5 lb Factory default setting
Short piping setting 18.3 lb
• During cooling the operating frequency of compressor is fuzzy logic controlled based on target Ps.
• The frequency of compressor goes down and Ps goes up; the frequency of compressor goes up and Ps goes
down.
• During cooling; if the low pressure reaches 152.3 psi, the LEV control of all indoor units will limit suction pressure
to 152.3 psi.
[Note]
The one-way connection piping of the units is generally dened as: when the longest piping is less than 98 ft (30m),
it is short piping; 98-295 ft (30-90m), medium piping; more than 295 ft (90m), long piping. The specic situation is
determined by installation in site.