Haier MRV5-H - 7.2.2 Rated Operation; 7.2.3 Trial Operation Confirmation

Haier MRV5-H
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Electric Wiring and Applications Cont.
3. System Status Display and Control (host)
SW1 SW2 SW3 Function Digital tube LD1 - 4 Display
0 0 2 Refrigerant type 410A represents 410A refrigerant
0 1 2
The same outdoor unit total number
and total capacity
LD1: The total number of outdoor unit
LD2: Display “-”
LD3/ LD4: Total outdoor unit capacity (unit: Horse)
For example: 3-48 said 3 outdoor machines, with a total
capacity of 48 horses
0 2 2 Total indoor unit capacity 50 represents 50 kbtu/h
0 3 2
The indoor units within the same
system
For example: 64
0 4 2 Number of indoor units working
Temperature sensor ON as a sign of the work of the
indoor unit
00 5 2
With the outdoor unit running mode
the same indoor unit number
For example: 13
0 6 2 Cooling target temperature
Unit: °F
0 7 2 Heating target temperature
0 8 2
Automatic recovery of refrigerant
NOTE: the end of the recovery
must be canceled or reset
When the outdoor stops, press START (SW5) for 2 s,
display 1111, start. (the outdoor is set to work in a state
of operation)
Press STOP (SW6) for 2 s, display 0000, stop
0 10(A) 2
Test run setup
NOTE: the end of the test run must
be canceled or reset
When the outdoor stops, press START (SW5) for 2 s,
display 1111, start. (the outdoor is set to work in a state
of operation)
Press STOP (SW6) for 2 s, display 0000, stop
0 11(B) 2 Outdoor unit mode 0-normal, C-only cool H-only heat
0 12(C) 2
Indoor unit expansion valve fully
open
Press START (SW5) for 2 s, display 1111, indoor
valve fully open 2 minutes, 2 minutes after the
automatic shutdown valve
0 13(D) 2 All the indoor unit for cooling
Press START (SW5) for 2 s, display 1111, fully open;
Press STOP (SW6) for 2 s, display 0000 closed
0 14(E) 2 All the indoor unit for heating
0 15(F) 2
Cancel all manual control (running
class)
Press START (SW5) for 2 s, display 1111 cancel; or
press STOP (SW6) for 2 s, display 0000, cancel
Remove all manual control (part), closed indoor unit