83
C. Cooling operation conrmation
 
Whether the cold air is blown out
Whether air circulation is in good 
condition
Whether the temperature
 
difference between return air and supply 
air is proper (Note 1)
Whether the operating voltage is 
proper (380 V ± 10%)
Whether operating pressure is 
normal (Note 3)
Whether the operating current
 
is at ± 15% of the standard value (at 
maximum frequency) (Note 2)
Set the operation to cooling mode and hold 
down the operation switch for more than 5
 
seconds in shutdown mode.
Make all the indoor units operate 
simultaneously
Normal
 operation condition of the 
compressor
 rotation direction of the blade
Check and
 
 the power supply 
voltage and circuit
 Check the temperature of indoor and outdoor;
 Check pipe length and charging amount of the
 
refrigerant;
 Check operating frequency of the compressor 
and operating condition of the outdoor fan;
 Check whether there is abnormal sound in the
 
compressor.
Start
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Check all indoor units one by one.
Once stop, the outdoor
 
unit can’t restart until 3 
to 5 minutes later.