95
FFailure 
code
Outdoor 
digital 
display tube: 
23-0,1
Indoor wired 
controller: 
17
Indoor unit LED status
LED5F ailure description: 
Discharging temperature sensor:
 Td1and Td2 failure
20 times
Outdoor unit LED status
LED1 LED2
Normal Normal
1. Model Failure diagnosis and troubleshooting
MRV 5-HR series 
DiagnosisT roubleshooting
2. Abnormity detection method
◆
Check if the sensor 
connection is normal;
◆
Check if resistance 
characteristic of the sensor is 
normal; 
◆
Check if the temperature 
loop acquired by the PCB is 
normal.
conditions
It is detected that the AD value 
is below 11 (open circuit) or 
above 1012 (short circuit) for 
60 seconds continuously. If 
detected after 3 minutes of 
compressor operation (AD 
value is below 11).
4. Possible causes
◆
The connection of sensor is 
not secure;
◆
The sensor is broken;
◆
The sensor is with 
resistance drift;
◆
The temperature acquired 
by PCB is not accurate.
Replace  it c orrectly by after-
sales personnel on site.
Check  i f  the  correspondin g 
connector of sensor is normal
Check  i f  resistanc e 
characteristic of the sensor 
is normal
Check  i f  the  temperatur e 
loop  a cquired  by  t he  
computer board is normal
Replace  it c orrectly by after-
sales personnel on site.
Replace  it c orrectly by after-
sales personnel on site.