160
Smart Power
BM1 (1-ON, 0-OFF)
Capacity (SW1-1→SW1-3) ESP selection
Room card
SW1-6
Unit Type
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-7 SW1-8 Description
ON OFF ON --- --- --- --- --- ADH071M1ERG
OFF ON ON --- --- --- --- --- ADH090M1ERG
--- --- --- OFF OFF --- --- --- 1st level(10Pa)(default)
--- --- --- OFF ON --- --- --- 2nd level(30Pa)
--- --- --- ON OFF --- --- --- 3rd level(50Pa)
--- --- --- ON ON --- --- --- 4th level(70Pa) (default)
--- --- --- --- --- OFF --- --- Room card unavailable
--- --- --- --- --- ON --- --- Room card available
--- --- --- --- --- ON OFF Medium ESP DUCT
ADH071M1ERG ADH090M1ERG
PCB code 0151800175B
SW2-1 SW2-2 SW2-3 SW2-4
Indoor unit Address
(Indoor unit address for one wired
controller control more than one
unit)
OFF OFF OFF OFF 0 (master)
OFF OFF OFF ON 1(slave)
OFF OFF ON OFF 2(slave)
OFF OFF ON ON 3(slave)
OFF ON OFF OFF 4(slave)
OFF ON OFF ON 5(slave)
OFF ON ON OFF 6(slave)
OFF ON ON ON 7(slave)
ON OFF OFF OFF 8(slave)
ON OFF OFF ON 9(slave)
ON OFF ON OFF 10(slave)
ON OFF ON ON 11(slave)
ON ON OFF OFF 12(slave)
ON ON OFF ON 13(slave)
ON ON ON OFF 14(slave)
ON ON ON ON 15(slave)
Wired controller communication address