For AD105/125/140M1ERG, ADH071M3ERG, ADH105/125/140/160/200/250H1ERG, static pressure level
selection can also /be achieved by Infrared remote controller, method is:
Step a: set the Infrared remote controller at condition:FAN mode, fan speed high.
Step b:then aim the remote controller at the infrared remote receiver RE 02, press HEALTH button 4+N times(1≤N
≤10, integer) within 12 seconds, then the receiver will beep N+1 times, the static pressure level N is been set
successfully.
Note:For Infrared remote controller YR HBS01,need press ON/OFF button make the controller's at OFF status
rstthen open the button cover press FRESH button will enter FAN mode interface.
Static pressure level (N)
External static pressure (pa)
ADH105H1ERG ADH125H1ERG
ADH140H1ERG ADH160H1ERG
ADH200H1ERG ADH250H1ERG
1 40 40
2 50 72
3 60 100
4 80 120
5 100 150
6 120 180
7 150 210
8 180 230
9 200 250
10 250 300