[文件標題] [日期]
34
Vol. 1.2 © 2020 Hanbell Precise Machinery Co., Ltd.
All rights reserved
supply
J5.3 P15V
LEM(CT) +15V power
supply
J5.4 V_LEM Phase V current
J6
J6.1 P24VI
THD +24V power
supply
J6.2 0VI THD 0V power supply
J7
J7.3 TPTOUR_AMB
Top Tour output(+)
isolated
J7.5 0V_AMB
Top Tour output(-)
isolated
J9
J9.1 Harmonic_Alarm_1A
Dry contact, open in
case of alarm
J9.2 Harmonic_Alarm_1B
Dry contact, open in
case of alarm
5.9 Variable Frequency Drive (VFD) Connector
Description of KEB inverter connection
RemarkThe figure is only for KEB, other brands may be different.
5.10 Parameter of inverter
Please refer KEB VFD parameter-1.1
X2A
Error (output of
passive switch)
Normal (output of
passive switch)