SERVICE DEPARTMENT : (724) 746-1100
BLOWER PURGE
DESICCANT
COMPRESSED
AIR DRYERS
INSTRUCTION MANUAL
HBP SERIES
Contents
1.0 General Safety Information ........................... 2
2.0 Receiving, Storing, and Moving ..................... 2
3.0 Description .................................................... 3
4.0 Installation ..................................................... 3
5.0 Instrumentation .............................................. 8
6.0 Operation ....................................................... 12
7.0 Maintenance .................................................. 29
8.0 Troubleshooting ............................................. 31
Drawings
P&ID Schematic Models 500 through 600 ............ 34
P&ID Schematic Models 750 through 4300 .......... 36
Electrical Schematic – 460VAC, 3 phase .............. 38
Electrical Schematic – 575VAC, 3 phase .............. 39
Electrical Schematic – 380VAC, 3 phase .............. 40
Electrical Schematic – 415VAC, 3 phase .............. 41
Electrical Data – Fusing & Wire Sizing .................. 42
WARRANTY .......................................................... 44
MODELS
RATED
FLOW
MODEL
REFERENCE
HBP500
HBP600
HBP750
HBP900
HBP1050
500 SCFM
600 SCFM
750 SCFM
900 SCFM
1050 SCFM
500
600
750
900
1050
HBP1300
HBP1500
HBP1800
HBP2200
HBP2600
1300 SCFM
1500 SCFM
1800 SCFM
2200 SCFM
2600 SCFM
1300
1500
1800
2200
2600
HBP3200
HBP3600
HBP4300
3200 SCFM
3600 SCFM
4300 SCFM
3200
3600
4300
3158050 Rev. E 1/08
XX-XXX-X
Internal Use Only
3158050e / 080102

Questions and Answers

  • S
    schneiderkristenAug 21, 2025
    What causes a High Humidity Alarm on the Left or Right Tower of my HANKISON HBP3200 Dehumidifier?
    • W
      William LeonAug 21, 2025
      If the HANKISON Dehumidifier displays a High Humidity Alarm on either the Left or Right Tower, this could be due to a desiccant bed overload. Check the inlet air flow rate, temperature, and pressure; if the flow and temperature are higher than the design specifications, or the pressure is lower, this can overload the dryer. Another cause could be a damaged or defective dew point sensor or monitor, so examine the sensor for physical damage and check the monitor/sensor operation, replacing them as necessary. Finally, a loss of desiccant drying capacity might be the issue. Check the filter elements and drains for improper filtration causing desiccant contamination, and repair or replace as needed. It may also be that the desiccant's useful life has been exceeded.
  • S
    Shawn SalinasAug 28, 2025
    What does it mean when my HANKISON HBP3200 shows a Blower Motor Overload Alarm?
    • K
      Kelly VasquezAug 28, 2025
      If the HANKISON Dehumidifier displays a Blower Motor Overload Alarm, it could be due to restricted or blocked purge air flow. Check the intake filter on the blower for dirt; examine the filter element and clean or replace it. It could also be due to a line failure. Check the voltages and currents in the motor circuit.
  • M
    melissakochSep 2, 2025
    What causes a Heater Over-Temperature Alarm on my HANKISON HBP3200 Dehumidifier?
    • C
      Corey HowardSep 2, 2025
      If the HANKISON Dehumidifier displays a Heater Over-Temperature Alarm, it could be due to insufficient purge gas flow. Check for purge blockage and temperature sensor failure. Another cause could be a temperature sensor failure; repair and replace as required.
  • T
    thompsonjulieSep 4, 2025
    What should I do if my HANKISON HBP3200 Dehumidifier displays a Heater Low-Temperature Alarm?
    • R
      Rodney JenkinsSep 4, 2025
      If the HANKISON Dehumidifier displays a Heater Low-Temperature Alarm, this could be due to a heating malfunction caused by heater failure or heater contactor failure. Replace the heater or heater contactor. It could also be due to a temperature sensor failure; repair and replace as required.
  • B
    bmillerSep 6, 2025
    What does an Energy Management Under-Range or Over-Range Alarm on my HANKISON HBP3200 Dehumidifier mean?
    • M
      Michelle MaloneSep 6, 2025
      If the HANKISON Dehumidifier displays an Energy Management Under-Range Alarm or Energy Management Over-Range Alarm, it might be due to an Energy Management sensor failure. Check the circuit for continuity and repair or replace as necessary.
  • S
    Shane SmithSep 8, 2025
    How to troubleshoot indicator lights not illuminated on HANKISON Dehumidifier?
    • N
      Nicholas FieldsSep 8, 2025
      If the indicator lights on the HANKISON Dehumidifier are not illuminated, there could be several reasons. First, there might be no power to the unit, so check the voltage at the terminal board. Second, there might be a loss of power supply to (or at) the dryer’s electrical disconnect switch or breaker (customer supplied); check if the disconnect switch or breaker is closed, and if a tripped breaker or blown fuse is noted, investigate and remedy the cause. Third, a blown fuse could be the problem, so replace the fuse. Finally, there could be a board malfunction, so replace the board.
  • R
    richardcolemanSep 12, 2025
    What does it mean when my HANKISON HBP3200 displays a Temperature Under-Range or Over-Range Alarm on the Left or Right Tower?
    • D
      David WarrenSep 12, 2025
      If the HANKISON Dehumidifier shows a Temperature Under-Range or Temperature Over-Range Alarm on either the Left Tower or Right Tower, it could be due to a tower temperature sensor failure. An Under-Range alarm may indicate a short circuit on the sensor, while an Over-Range alarm may indicate an open circuit on the sensor. Check the temperature circuit for continuity and repair or replace as necessary.
  • A
    Arthur ParkerSep 13, 2025
    What to do if my HANKISON HBP3200 Dehumidifier displays a Dew Point Under-Range or Over-Range Alarm during regeneration?
    • N
      nealedwardSep 13, 2025
      If the HANKISON Dehumidifier displays a Dew Point Under-Range or Dew Point Over-Range Alarm on either the Left Tower or Right Tower while regenerating, it could be due to an Energy Management temperature sensor (RTD4) failure. Check the temperature circuit for continuity and repair or replace as necessary.
  • B
    Brian StevensSep 15, 2025
    Why is there excessive pressure drop in my HANKISON HBP3200 Dehumidifier?
    • A
      Angela RichardSep 15, 2025
      If you're experiencing excessive pressure drop in your HANKISON Dehumidifier, it could be due to a couple of reasons. The inlet/outlet screens on the desiccant towers might be dirty; clean the screens following the desiccant removal instructions in the Maintenance section. Alternatively, the flow rate might be excessive; check the flow rate of the inlet air and reduce it to the design flow rate.
  • J
    Jacob RamirezNov 18, 2025
    What to do if the HANKISON HBP3200 shows an Outlet Dew Point Alarm on the Left or Right Tower?
    • D
      Dr. Laura WangNov 18, 2025
      If the HANKISON Dehumidifier displays an Outlet Dew Point Alarm on either the Left or Right Tower, several factors could be responsible. It might be due to the inlet air flow being higher than the sizing condition, in which case you should reduce the inlet flow. Another cause could be liquids entering the dryer inlet; inspect the prefilter and drain valve, and clean, repair, or replace the automatic drain valve as needed. The inlet air temperature might be higher than the sizing condition; check the compressor aftercooler and cooling system, and reduce the inlet air temperature. Desiccant dusting can also trigger this alarm, so check the air pressure, airflow, and airflow surges, correcting them as necessary, and consider replacing the desiccant. Contaminated desiccant (e.g., with oil) is ...

Summary

General Safety Information

Receiving, Storing, and Moving

Guidelines for inspecting, storing, and safely handling the dryer unit.

Installation

System Arrangement

Recommendations for dryer placement relative to other system components.

Electrical Connections

Instructions for making electrical connections to the dryer.

Instrumentation

Energy Management System

Overview of the optional system that optimizes dryer operation for energy savings.

Operation

Operating Modes

Explains the different automatic and manual modes for dryer operation.

Operating Sequence Description

Step-by-step explanation of the drying and regeneration cycles.

Control Board Jumpers

Configuration options for the dryer type, energy management, and dew point settings.

Operator Interface

Information on the front panel interface, LEDs, switches, and display.

Alarm & Service Mode

Explanation of how the controller indicates and manages alarms and service reminders.

Start-up

Steps for initial dryer setup, pressurization, and bringing it online.

Operational Check Points

Procedures for verifying dryer functionality during operation.

Dryer Shut Down

Steps for safely shutting down and depressurizing the dryer.

Loss of Power

Describes how dryer valves react and sequence resumes after power interruption.

Maintenance

Desiccant Replacement

Guidelines on desiccant replacement frequency, procedure, and quality.

Troubleshooting

Warranty

HANKISON HBP3200 Specifications

General IconGeneral
BrandHANKISON
ModelHBP3200
CategoryDehumidifier
LanguageEnglish