EasyManua.ls Logo

HARNITEK Thermopod - Controller Starting and Setting Procedures; Setting the Controller Time; Controller Settings Post Time Setup; Starting the System After Time Setting

HARNITEK Thermopod
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12 Controller Starting and Setting
For the first time when powering up the Thermopod,
the screen shall light up with blue colour.
The installer shall set up the local time by the following
steps,
Step 1: press the button
and hold it for 10
seconds until the time shown on the screen is flashing.
Step 2: press the button
, the hh shall be
flashing, and then adjust the time hh.
Step 3: press the button
, the mm shall be
flashing and then adjust the time mm.
Step 4: press the button
to confirm the
adjustment. After 6
0 seconds, the system shall be
automatically locked.
After time setting, start the system,
Step 1: press the button
and hold it for 1
second, then heating water signal appears.
Step 2: 1 second after heating water signal, the water
pump signal appears.
After 90 seconds, the
compressor shall automatically operate.
From now on, the system starts operation by default.
For further setting, please refer to the “Thermopod
Digital Controller Manual”.
Time setting:
After time setting:
13 System Commissioning
Turn the Thermopod on at the fused spur. After 30 seconds the digital controller on Thermopod shall light up and
show the current temperature of the cylinder and water outlet. The pump shall start to run. After 90 seconds of time
delay the compressor shall start operating.
Leave the system to operate for a minimum of 30 minutes and check the following,
1. Check if the default temperature for water heating in the controller is 53.
2. Check if the system is increasing the water temperature after 30 minutes.
(Standard: under 7 of ambient temperature in sunny day, it takes 40 minutes to increase water temperature from
30 to 35 in good quality 200 Litres of water cylinder.)
14 Tables of parameter and status
Unit parameter table
Parameter
Definition
Setting range
Default
Comments
L2
Compressor activating return temperature
difference
2
~18
5
L3
Cylinder Target temperature
35 ~ 60
53
Default 53, not over 60
Thermopod - Installation Manual 23 | Page