Section 3:
Start-Up
Copyright © 2011 Haskris Company 19 www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
2. Measure and record amperage and voltage at the Fan Motor
Inverter Contactor in main electrical enclosure.
3. Repeat the step 1 above to increase the head pressure value
to the original pre-set value of 220.
(Use the
key to increase the head pressure value.)
4. Press both
keys simultaneously when done to return
to the default display.
• Turn off the system once system is operating satisfactorily.
• Remove refrigerant manifold gauge.
• Close control box and replace all sheet metal panels on the R1600.