Maintenance Notes
Copyright © 2011 Haskris Company 50 www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
5.
Press the enter key to view the most recent fault. Record the value on the display
screen in the following table. Then press the “esc” key to return to the previous
screen.
Display Parameter
Display ParameterDisplay Parameter
Display Parameter
Error
ErrorError
Error
Code VFD A
Code VFD ACode VFD A
Code VFD A
Error Code VFD B
Error Code VFD BError Code VFD B
Error Code VFD B
U3-01
U3-02
U3-03
U3
-
04
U3-05
U03-06
U03-07
U03-08
U03-09
U03-10
6. Press the up arrow key to set the display to “U3-02”. This will display the second most
recent fault in the VFD. Press enter again to view the fault code.
7.
Repeat the previous two steps and check all of the parameters. The VFD can store the
10 most recent faults.
If the screen reads “- -” then there are no further faults recorded.
8.
Press the “esc” key until you return to the first screen reading “F 0.00”
Table 3 Fault Codes