36
Admittance Smart Switch Series
Manual
Rev 1.2, June 2008
37
SPECIFICATIONS
Operating Voltage
• 7 - 30Vdc (residual ripple no greater than
100mV)
• 80 - 260Vac 50/60Hz
Power Consumption
• <0.8W @ 24Vdc
• <5VA @ 240Vac
• <3VA @ 115Vac
Communications
• GosHawk, Modbus
• Remote version also with HART,
Probus DP and DeviceNet (options)
• Multidrop mode can address 1-250 units
over 4 wires
Relay Output: (1) SMART (2) Remote
• Form ‘C’ (SPDT) contacts, rated 5A at
240Vac resistive
• Remote failsafe test facility for one relay.
Measurement Range
• 0.2pF - 100nF
Resolution
• 0.01 pF
Electronic Accuracy
• 0.05 pF
Stability
• 0.01% / °C
Operating Temperature
Remote electronics -40°C (-4F) to 80°C (176°F)
Smart Probe -4C (-40°F) to 450°C 842°F)*
Remote Probe -4C (-40°F) to 450°C (842°F)*
Probe/Amplier Separation
• up to 500m (1640ft) using specied exten-
sion cable
Cable type between Amplier and Probe
• 4 conductor shielded twisted pair instrument
cable.
Conductor size dependent on cable length.
BELDEN 3084A, DEKORON or equivalent.
Max: BELDEN 3084A = 500m (1640 ft)
Max: DEKORON IED183AA002 = 350m
(1150 ft)
Maximum Operating Pressure
• 2 BAR
Display (Remote version only)
• 2 line x 12 character alphanumeric LCD
• Backlight standard
Memory - Remote
• Non-Volatile (No backup battery required)
• >10 years data retention
Enclosure Sealing
• Smart Probe IP67
• Remote Electronics IP65 (Nema 4x)
• Remote Probe IP67
Cable Entries
BSP process mounting
• 2 x M20 glands
NPT process mounting
• 2 x 3/4” NPTF threaded adaptors
Remote
3 x 20mm (0.8), 1 x 16mm (0.6) knock outs
Mounting
• 3/4” NPT or BSP Thread
• 1” NPT or BSP Thread
• 1.5” NPT or BSP Thread
• 50mm (2”) Flange (ANSI, DIN or JIS
patterns available)
Remote Test Input
Press to test
(used to check for malfunction of
unit from remote position, PLC, SCADA etc)
*correct temperature range probe must be specied when ordering
Patents Pending