EasyManua.ls Logo

Heat Controller HBH Series - Page 17

Heat Controller HBH Series
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering Design Guide HBH SERIES Heat Controller, Inc.
17
Blower Performance Data - HBH120 Standard Unit
All Data is Wet Coil
Table Continued from Previous Page
SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
4000
BHP 1.63 1.71 1.78 1.86 1.94 2.03 2.11 2.19 2.27 2.37 2.45 2.51 2.59 2.67 2.75 2.85
Sheave/Mtr A A A A A A A A A A A A C C C C
RPM 865 895 920 950 980 1010 1035 1060 1085 1115 1140 1160 1185 1210 1235 1260
Turns Open 6 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1 1 3.5 3 2.5 2
4100
BHP 1.73 1.81 1.90 1.97 2.05 2.12 2.20 2.27 2.34 2.42 2.52 2.62 2.70 2.80 2.90
Sheave/Mtr A A A A A A A A A A A C C C C
RPM 885 915 945 970 1000 1025 1055 1080 1105 1130 1155 1180 1200 1225 1250
Turns Open 6 5.5 4.5 4 4 3 2.5 2 2 1.5 1 3.5 3 2.5 2
4200
BHP 1.87 1.94 2.02 2.08 2.16 2.24 2.32 2.40 2.48 2.58 2.68 2.76 2.86 2.96
Sheave/Mtr A A A A A A A A A A C C C C
RPM 905 935 965 990 1020 1045 1070 1095 1120 1145 1170 1190 1215 1240
Turns Open 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1 3.5 3.5 3 2.5
4300
BHP 2.00 2.07 2.16 2.23 2.31 2.41 2.49 2.57 2.66 2.74 2.84 2.94 3.02 3.15
Sheave/Mtr A A A A A A A A A C C C E E
RPM 930 955 985 1010 1035 1065 1090 1115 1140 1160 1185 1210 1230 1255
Turns Open 5 4.5 4 3.5 3 2.5 2 1.5 1.5 4 3.5 3 2.5 2
4400
BHP 2.14 2.22 2.32 2.40 2.48 2.56 2.65 2.74 2.82 2.92 3.00 3.10 3.18
Sheave/Mtr A A A A A A A A A C E E E
RPM 950 975 1005 1030 1055 1080 1110 1135 1155 1180 1200 1225 1245
Turns Open 4.5 4 3.5 3 3 2.5 2 1.5 1 4 3 3 2.5
4500
BHP 2.30 2.38 2.46 2.54 2.62 2.72 2.80 2.88 3.00 3.08 3.16 3.26
Sheave/Mtr A A A A A A A A D E E E
RPM 970 995 1020 1045 1070 1100 1125 1145 1170 1195 1215 1240
Turns Open 4.5 4 3.5 3 2.5 2 1.5 1.5 1 3.5 3 2.5
4600
BHP 2.39 2.45 2.54 2.63 2.72 2.83 2.92 3.00 3.10 3.18 3.28 3.38
Sheave/Mtr A A A A A A A D D E E E
RPM 980 1000 1025 1050 1075 1105 1130 1150 1175 1195 1220 1245
Turns Open 4 3.5 3.5 3 2.5 2 1.5 1 1 3.5 3 2.5
4700
BHP 2.46 2.52 2.62 2.72 2.82 2.92 3.02 3.12 3.22 3.32 3.40 3.50
Sheave/Mtr A A A A A A D D E E E E
RPM 985 1005 1030 1055 1080 1105 1130 1155 1180 1205 1225 1250
Turns Open 4 3.5 3 2.5 2 1.5 1.5 1 4 3.5 2.5 2.5
4800
BHP 2.57 2.64 2.74 2.84 2.94 3.04 3.14 3.24 3.32 3.42 3.52 3.60
Sheave/Mtr A A A A A D D D E E E E
RPM 990 1010 1035 1060 1085 1110 1135 1160 1180 1205 1230 1250
Turns Open 4 3.5 3 2.5 2 1.5 1 1 3.5 3 2.5 2
4900
BHP 2.68 2.78 2.88 3.00 3.06 3.16 3.26 3.36 3.44 3.54 3.64 3.75
Sheave/Mtr A A A D D D D E E E E E
RPM 995 1020 1045 1070 1090 1115 1140 1165 1185 1210 1235 1255
Turns Open 3.5 3 3 2.5 1.5 1.5 1 4 3.5 3 2.5 2
5000
BHP 2.82 2.92 3.00 3.10 3.20 3.28 3.38 3.48 3.56 3.66 3.74
Sheave/Mtr A A D D D D D E E E E
RPM 1005 1030 1050 1075 1100 1120 1145 1170 1190 1215 1235
Turns Open 3.5 3 2.5 2 1.5 1 1 3.5 3 2.5 2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All air ow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

Related product manuals