EasyManua.ls Logo

Heat Controller HTV Series - CONDENSATE PIPING

Heat Controller HTV Series
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HTV/HTD/HTH SERIES Heat Controller, Inc.
7
INSTALLATION
SOUND ATTENUATION
Sound attenuation is achieved by
enclosing the unit within a small
mechanical room or a closet. Additional
measures for sound control include the
following:
1. Mount the unit so that the return air
inlet is 90° to the return air grille.
Refer to Figure 3. Install a sound
bae as illustrated to reduce line-of
sight sound transmitted through
return air grilles.
2. Mount the unit on a rubber or
neoprene isolation pad to minimize
vibration transmission to the building
structure.
CONDENSATE PIPING
These units utilize a condensate hose
inside the cabinet as a trapping loop;
therefore an external trap is not
necessary. Figure 4A shows typical
condensate connections. Figure 4B
illustrates the internal trap for a typical
vertical heat pump. Each unit must be
installed with its own individual vent
(where necessary) and a means to ush
or blow out the condensate drain line.
Do not install units with a common trap
and/or vent.
Figure 4A: Condensate Drain Air
Figure 3: Vertical Sound Attenuation
8
Figure 4B: Internal Condensate Trap
NOTICE! Units with clear plastic drain
lines should have regular maintenance
(as required) to avoid buildup of debris,
especially in new construction.

Other manuals for Heat Controller HTV Series

Related product manuals