30EPU‐DInstallationandOperationManual
059840‐00Rev.A Heat‐TimerCorp.
DayAdjustment
NightAdjustment
DayCutoff
Selections:AthroughP Default:E
MenuPath:/SystemSettings>DayHeatAdjust
Description:
ControlsthelengthoftheCycle‐ONsegmentbasedontheoutdoortemperatureascomparedtotheDay
Cutoffsetting(see“DayCutoff”onpage 30)duringdaytimeoperation.Setting“A”isthelowestsetting(less
heat),“P”isthehighestsetting(mostheat).
Duringdaytimeoperation,ifthebuildingistoocold,settheDayAdjustmentoneletterhigher,ifthebuildingis
toohot,settheDayAdjustmentoneletterlower.Wait24hourstoevaluatethenewsettingbeforemakingany
additionaladjustments.
See“CycleLength”onpage 5formoreinformation.
Selections:AthroughP Default:D
MenuPath:/SystemSettings>NightHeatAdjust
Description:
ControlsthelengthoftheCycle‐ONsegmentbasedontheoutdoortemperatureascomparedtotheNight
Cutoffsetting(see“NightCutoff”onpage 31)duringnighttimeoperation.Setting“A”isthelowestsetting
(lessheat),“P”isthehighestsetting(mostheat).
Duringnighttimeoperation,ifthebuildingistoocold,settheNightAdjustmentoneletterhigher,ifthe
buildingistoohot,settheNightAdjustmentoneletterlower.Wait24hourstoevaluatethenewsetting
beforemakinganyadditionaladjustments.
See“CycleLength”onpage 5formoreinformation.
Selections:20°F/-7°C(on)
100°F/38°C(off)
Default:55°F/13°C
MenuPath:/SystemSettings>DayCutoff
Description:
SetstheoutdoordaytimetemperaturecutoffforwhentheEPU‐Dcallsforheat.
Whentheoutdoortemperaturefallsbelowthecutoff,thecontrolbeginsrunningcyclesandprovidingsteam
totheheatingsystem.
Whentheoutdoortemperaturerisesto2°Fabovethecutoff,thecontrolstopsprovidingsteamtotheheating
system.