11 Electrical connection
44 Digital Governor Basic System PANDAROS II
The allowed length and necessary cross-sections of the cables to connect are as follows:
L 1 Power supply max. 15 m 2 x 2,50 mm²
L 2.1 Actuator feedback 3 x 0,75 mm² shielded
L 2.2 Actuator drive up to 10 m 2 x 2,50 mm²
over 10 … 20 m 2 x 4,00 mm²
L 3.1 Setpoint potentiometer 3 x 0,75 mm² shielded
L 3.2 4 ... 20 mA input 2 x 0,75 mm²
L 3.3 0 … 5 V input 2 x 0,75 mm² shielded
L 3.4 Synchronizer 2 x 0,75 mm² shielded
L 3.5 Load measuring unit 2 x 0,75 mm² shielded
L 4 Magnetic pick-up 2 x 0,75 mm² shielded
L 5.1 Temperature sensor 2 x 0,75 mm²
L 5.2 Boost pressure sensor 2 x 0,75 mm²
L 5.3 Oil pressure sensor 2 x 0,75 mm²
L 6.1 Engine stop 1 x 0,75 mm²
L 6.2 Increase speed 1 x 0,75 mm²
L 6.3 Decrease speed 1 x 0,75 mm²
L 6.4 other switch functions 1 x 0,75 mm²
(the switches have to be supplied with battery plus)
L 7 Error message 1 x 0,75 mm²
(the error lamp has to be supplied with battery plus, ground is switched)
L 13 CAN communication with DGM 02 2 x 0,14 mm² shielded