PN/CAN Gateway, PROFINET/CANopen Slave | Version 2 | 1/26/2021 34
7.5 PROFINET Diagnostic messages
The PN/CAN Gateway supports the following diagnostic alarms:
1 Configuration error: Node-ID > 0 is not allowed for a configuration with DCF file
2 According the EDS/DCF configuration the configured SDO cannot be written.
3 The configured SDO is not available in the EDS/DCF configuration.
4 Configured SDO length does not correspond to that in the EDS/DCF configuration.
5 The Consumer-Heartbeat Node-ID cannot be the Node-ID of the device.
6 Unknown module type used (perform firmware update if necessary)
7 Node ID must be > 0 because no DCF configuration is used.
8 SDO with same index is used in at least two modules
9 EDS/DCF project is too big
10 SDOs with data type "Visible String" or "Octet String" cannot be used in slots