9
Menu navigation and adjustment values
44
Table 9.1: Operation mode "Screed drying"
Bake out day
Flow set
temperature in
°C
If screed drying gets interrupted, resume
drying as follows:
1
25
Day of interruption
resume from day
2
30
0 – 15
1
3
35
16
16
4
40
17 – 23
17
5 – 12
45
24 – 28
24
13
40
29
29
14
35
15
30
16
25
17 – 23
10
24
30
25
35
26
40
27
45
28
35
29
25
30
0
figure 9.2: Flow must temperature in dependence of the bake out days at „Screed drying”
Flow must temperature [°C]
Bake out days