Fault reports and their corrections
74
No.
Fault report
Cause of fault
Fault correction
236
Extinguishing water
Input at Alarm-Modul has triggered
*Quit fault
237
Storage room level
Input at Alarm-Modul has triggered
*only Display
238
ALARMMODUL
CAN communication to the alarm-
module is interrupted
**Check connection module
CANBus
*Check module
✆ - contracting party
239
External transport
technology
Input at Alarm-Modul has triggered
*Quit fault
240
Water shortage
Input at Alarm-Modul has triggered
*Quit fault
241
Waste water pump
Input at Alarm-Modul has triggered
*only Display
242
Supply air error
Input at Alarm-Modul has triggered
*Quit fault
247
SPECIAL EXPANSION
CAN communication to the alarm-
module is interrupted
*Check connection module CANBus
*Check module
✆ - contracting party
248
LOGGINGMODUL
CAN communication to the alarm-
module is interrupted
*Check connection module CANBus
*Check module
✆ - contracting party
249
AUTOREBOOT 2
Control restarted due to overload
(e.g. network overload)
Reboot of the Control
adjust Network configuration
250
AUTOREBOOT 24
Software-monitoring fault
✆ - contracting party
251
AUTOREBOOT 50
Software-monitoring fault
✆ - contracting party
252
AUTOREBOOT 51
Software-monitoring fault
✆ - contracting party
253
AUTOREBOOT 67
Software-monitoring fault
✆ - contracting party
254
AUTOREBOOT 68
Software-monitoring fault
✆ - contracting party