2.3.5 Status indication
Should the meter cover be opened, S2 will be indicated.
Should the terminal cover be opened, S3 will be indicated.
Should the meter have been overloaded, S4 will be indicated.
Should the meter cover and terminal cover open detection be deactivated, S5 will be
indicated.
Should the meter be in factory mode, S7 will be indicated.
2.3.6 Display contents
Display item
OBIS code
Data display format
Total energy consumption
1.8.0
XXXXXX.XX
Reverse energy consumption
2.8.0
XXXXXX.XX
Date
0.9.2
DD-MM-YY
Time
0.9.1
hh:mm:ss
Voltage of phase A
32.7.0
XXX.X
Voltage of phase B
52.7.0
XXX.X
Voltage of phase C
72.7.0
XXX.X
Current of phase A
31.7.0
XXX.XXX
Current of phase B
51.7.0
XXX.XXX
Current of phase C
71.7.0
XXX.XXX
Active power of phase A
21.7.0
XX.XXXX
Active power of phase B
41.7.0
XX.XXXX
Active power of phase C
61.7.0
XX.XXXX
Power factor of phase A
33.7.0
X.XXX
Power factor of phase B
53.7.0
X.XXX
Power factor of phase C
73.7.0
X.XXX
Power grid frequency
14.7.0
XX.XX
Phase A and B angle
81.7.1
XXX.X
Phase A and C angle
81.7.2
XXX.X
Credit Balance
c.51.0
XXXXXX.XX
Maximum power
1.35.0
XX.XXXX