2.8 Load control
When the loaded active power exceeds value A (Maxim power) and the duration of this
load exceeds the entered delay time B, the relay is disconnected.
The relay will remain disconnected until a period of time C, upon which the relay is again
reconnected, and then the load control detection function is again repeated.
If overload event occurs 5 times, a waiting time of period D is enacted and then the
number of overload events is reset and the relay is reconnected and the load control
detection function is again repeated.
If no overload occurs during time E, the number of overload events is reset.
Note: Should power on/off, set Max power or clear event record while in the controlling
process, the status of load control will be reset.