Harrington Generators International
498-1084 20 HRD060D Diesel Generator
Operation
Icon Alarm / Warning Description
BATTERY UNDER VOLTAGE /
BATTERY OVER VOLTAGE
The DC supply has fallen below
or risen above the low/high volts
setting level.
CHARGE FAILURE
The auxiliary charge alternator
voltage is low as measured from
the W/L terminal.
ENGINE HIGH TEMPERATURE
The module detects that the
engine coolant temperature
has exceeded the high engine
temperature pre-alarm setting
level after the “Safety On” timer
has expired.
LOW FUEL LEVEL
The level detected by the fuel level
sensor is below the low fuel level
setting.
LOW OIL PRESSURE
The module detects that the
engine oil pressure has fallen
below the low oil pressure pre-
alarm setting level after the “Safety
On” timer has expired.
INTERNAL MEMORY ERROR
Either the conguration le or
engine le memory is corrupted.
Contact MTC for assistance.
GENERATOR OVER VOLTAGE
The generator output voltage has
risen above the pre-set pre-alarm
setting.
GENERATOR UNDER VOLTAGE
The generator output voltage has
fallen below the pre-set pre-alarm
setting after the Safety On timer
has expired.
GENERATOR OVER
FREQUENCY
The generator output frequency
has risen above the pre-set pre-
alarm setting.
GENERATOR UNDER
FREQUENCY
The generator output frequency
has fallen below the pre-set pre-
alarm setting after the Safety On
timer has expired.
FAIL TO START
The engine has not red after the
preset number of start attempts.
FAIL TO STOP
The module has detected a
condition that indicates that the
engine is running when it has been
instructed to stop.
NOTE: ‘Fail to Stop’ could indicate
a faulty oil pressure sensor – If
engine is at rest check oil sensor
wiring and conguration.
Common Alarms
The common alarm indicator will be illuminated when
there is a condition with the engine or alternator that
requires the operator’s attention. When the common
alarm indicator is illuminated one of the following icons
will be displayed on the modules LCD.
More information about the DSE3110 control module
can be found in Manufacturer’s Service and User
Guides section of this manual.
Remote Connection Terminal
These are to be used to connect the set to a remote
Automatic Mains Failure (AMF) panel, remote
control panel or timer volt free switch. The switched
connection can then transmit a start and stop signal
to the DSE3110 to initiate the generator start up or
shutdown procedure.
Remote Start Controller
HGI can supply remote start controllers (e.g CN222)
whioch are read for easy connection via a buccaneer
plug for connecting into the socket on the generator
control panel.
Contact HGI Sales for further information on the types
of remote start panels available for your generator.