4.
Bury cables.
Note
Interconnecng cable (available for two pedestals and above): The recommended length is L
+1.5 m.
Network communicaon cable: It is recommended to use CAT5e or the network cable has
beer performance.
The suggested external diameter of the low voltage conduit is 30 mm.
If more peripherals are required to connect, you should increase the conduit diameter or bury
another conduit for the external cables.
Before digging holes, evaluate the thickness of the
installaon surface to avoid puncturing.
When slong on the installaon surface, pay aenon to the posion and width of the slot to
avoid misalignment of the barrier.
One distribuon cabinet supplies one pedestal.
The maximum allowable diameter of the power cable is 12 AWG (UL1015), and the
transmission distance is 100 m.
One
distribuon cabinet supplies two pedestals.
The maximum allowable diameter of the power cable is 16 AWG (UL1015), and the
transmission distance is 25 m.
DS-K3BC430LX Series Swing Gate