Fire Source Detecon
The funcon is developed to detect the re source in the detecon area. If re sources are spoed
and the duraon reaches the seng, the re alarm will be triggered and a series of operaons will
be executed.
Before You Start
Note
Indoor Channel Blockage Detecon and On/O Work Detecon will be out of service when Fire
Source Detecon is enabled.
Steps
1.
Click
Conguraon → Event → Smart Event → Fire Source Detecon .
2.
Check Enable.
3.
Set
detecon area and disabled area.
1) Click Draw Detecon Area /Draw Disabled Area.
2) Le-click to draw a convex quadrilateral.
3) Repeat step a and step b to draw less than 4
detecon areas/disabled areas.
4) Oponal: You can edit the areas you drew as follows.
●
Hover mouse inside an area and drag to change its
locaon.
●
Hover mouse on the vertexes of an area and drag to adjust the their locaons.
●
Click Clear All to delete all areas exist.
Device will process smart
detecon and analysis on events in detecon areas and neglect
feedbacks from desabled areas.
4.
Set
detecon parameters.
Time Threshold(s)
If re sources are spoed and the duraon reaches the me seng, the re alarm will be
triggered.
Sensivity
The more sensive the detecng funcon is, the more easily the alarm will be triggered and
the more likely to misidenfy.
5.
Set arming schedule. See Set Arming Schedule .
6.
Set linkage method. See Linkage Method Sengs .
7.
Click Save.
Set
On/O Work Detecon
The funcon is developed to detect whether the sta are on duty. If the number of detected
persons in the zones does not reach the
sengs and the duraon reaches the me sengs, a
series of operaons will be executed.