3 Product Description F2 DO 16 02
Page 22 of 42 HI 800 139 E Rev. 2.00
Relay outputs
Relay types
for each channel
2 safety relays with forcibly guided contacts,
1 standard relay
Number of outputs 16 potential-free normally open contacts
Switching voltage
5 V, 30 VAC / 60 VDC
Switching current
10 mA, 3 A,
internally fused with 3.15 A,
fuse breaking capacity: 100 A
Contact material Silver alloy (AgNi)
Switching time approx. 30 ms
Reset time approx. 10 ms
Bounce time approx. 15 ms
Contact life time
mechanical
electrical
10 x 10
6
switching operations
See Figure 4
Table 12: Specifications for the Relay Outputs
Relay output switching capacity (general safety applications)
≤ 30 VDC max. 90 W (3,15 A)
Switching capacity DC
induction-free
1)
≤ 60 VDC max. 24 W (0,4 A)
Switching capacity AC
induction-free
1)
≤ 30 VAC max. 90 VA
Switching capacity AC
cos φ > 0,5
≤ 30 VAC max. 50 VA
Switching capacity DC,
UL 508
24 VDC bei 1 A, resistive
1)
Switching capacity AC,
UL 508
250 VAC bei 6 A, GP
1)
Circuit induction-free
- Free-wheeling diode
- Use suitable protective circuit, e.g., RC elements, Zener diodes or varistors
Table 13: Relays Output Switching Capacity