4 Start-up F2 DO 16 02
Page 28 of 42 HI 800 139 E Rev. 2.00
4.3.2.1 Tab Module
The Module tab contains the following system parameters:
System parameter
Data
type
R/W Description
DO.Error Code WORD R Error codes for all digital outputs
Coding Description
0x0001 Module fault
0x0002 Safety switch 1 faulty
0x0004 Safety switch 2 faulty
0x0008 FTT test of test pattern faulty
0x0010 Read back channels faulty
0x0020 Active shutdown faulty
0x0040 Errors during initialization relay
0x0080 FTT test: error in the relay voltage
0x0100 FTT test of CS (chip select) signals faulty
0x0400 FTT test: 1st temperature threshold exceeded
0x0800 FTT test: 2nd temperature threshold exceeded
0x1000 Status of safety switch 1
0x2000 Status of safety switches
0x4000 Active shutdown via watchdog faulty
0x8000 Test of the relay voltage provides a fault
Module Error Code WORD R Module error code
Coding Description
0x0000
I/O processing, if required with errors, see other
error codes
0x0001 No I/O processing (CPU not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: invalid configuration
0x0020 No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS UDINT R Slot number (System Rack Slot)
Module Type UINT R Type of module, target value: 0x00F1 [241
dec
]
Table 18: SILworX - System Parameters for Digital Outputs, Module Tab