F2 DO 16 02 4 Start-up
HI 800 139 E Rev. 2.00 Page 29 of 42
4.3.2.2 Tab DO 16: Channels
The DO 16: Channels tab contains the following system variables.
System parameter Data type R/W Description
-> Error Code
[BYTE]
BYTE R Error codes for the digital output channels
Coding Description
0x01 Error in the digital output module
0x04 Error while reading back the digital outputs
0x10
Error while reading back the status relay [x].1
(the channel is permanently de-energized)
0x20
Error while reading back the status relay [x].2
(the channel is permanently de-energized)
0x80
The channel cannot be switched on after a shut
down triggered by e.g., the user program,
forcing, a channel fault or a module fault.
Value [BOOL] -> BOOL W Output value for DO channels:
1 = output energized
0 = output de-energized
Table 19: SILworX - System Parameters for Digital Outputs, DO 16: Channels Tab