(APPENDIX IV) DIMENSIONS, WIRING AND MECHANICAL PARTS | PAGE 62
For proper protection of the equipment, the following elements must be installed
in the electrical panel:
FUSES
AMPS
F0
General Positive Power
40
F1
Digital Automatic Control Unit CEC7
4
F2
Phase U
2
F3
Phase V
2
F4
Phase W
2
F5
Differential Relay + Tripping Coil
2
F6
Battery Charger
4
The negative terminal of the battery, the chassis of the electrical panel and the
chassis of the generator set must all be earthed.
Maximum height assigned above sea level is 2000m.