47
EMC and immunity
EMC interference
immunity
IEC/EN 61850-
3:2002 EMI TYPE
tests, test in comp.
with
Description Test level
IEC/EN 61000-4-2 Electrostatic discharge
Contact discharge ± 8 kV
Air discharge ± 15 kV
IEC/EN 61000-4-3 Electromagnetic field
80 MHz ... 2700 MHz 20 V/m
IEC/EN 61000-4-4 Fast transients (burst)
DC Power Line ± 4 kV
AC Power Line ± 4 kV
Data line ± 4 kV
IEC/EN 61000-4-5 Voltage surges
DC Power Line ± 2 kV line/ground; ± 1 kV line/line
AC Power Line ± 4 kV line/ground; ± 2 kV line/line
Data line ± 4 kV line/ground
IEC/EN 61000-4-6 Conducted disturbances
150 kHz ... 80 MHz 10 V
IEC/EN 61000-4-12 Damped oscillation
DC Power Line ± 2,5 kV line/earth; ± 1 kV line/line
AC Power Line ± 2,5 kV line/earth; ± 1 kV line/line
Data line ± 2,5 kV line/earth; ± 1 kV line/line
IEC 60255-5 dielectric strength
DC Power Line, power unit type „L“ 500 V AC
500 V AC
AC Power Line, power unit type
„M“
2000 V AC
2000 V AC
DC Power Line, power unit type
„M“
2000 V AC
signal contact type „L“ and „M“ 2000 V AC
EMC interference
immunity
IEEE 1613:2009
EMI TYPE tests,
test in comp. with
Description Test level
IEEE C37.90.3 Electrostatic discharge
Contact discharge ± 8 kV
Air discharge ± 15 kV
IEEE C37.90.2 Electromagnetic field
80 MHz ... 1000 MHz 35 V/m (peak)
IEEE C37.90.1 Fast transients (burst)
DC Power Line ± 4 kV
AC Power Line ± 4 kV
Data line ± 4 kV