Grounding the device
The device is grounded via the separate grounding screw on the back of
the device.
Use a wire diameter for the ground conductor that is no smaller than
the diameter of the supply voltage connection, however of at least 1.0
mm² (AWG16).
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
Shielded ground
The shielded ground wire of the twisted pairs cables is connected to the
front panel as a conductor.
Beware of possible short circuits when connecting a cable section with
conductive shield braiding.
Supply voltage
The supply voltage is electrically isolated from the housing.
Connect only a supply voltage that corresponds to the type plate of your
device.
Every time you connect the electrical conductors, make sure that the
following requirements are met:
The power supply conforms to overvoltage category I or II.
The power supply has an easily accessible disconnecting device
(e.g., a switch or a plug). This disconnecting device is clearly
identified. So in the case of an emergency, it is clear which
disconnecting device belongs to which power supply cable.
The electrical wires are voltage-free.
The ground screw on the back of the device is connected to the
protective conductor.
There is a fuse in the outer conductor (AC) or the positive
conductor (DC) of the voltage supply.
Regarding the properties of this fuse: See “General technical data”
on page 43.
Supply with DC voltage: the fuse is suitable for a DC voltage.
If the neutral conductor (AC) or the negative conductor (DC) is not
grounded: there is a fuse in each of the two wires.
The wire diameter of the power supply cable is at least 1 mm²
(North America: AWG16) on the supply voltage input.
The cross-section of the protective conductor is the same size as
or bigger than the cross-section of the power supply cables.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hirschmann MAR1040 and is the answer not in the manual?

Hirschmann MAR1040 Specifications

General IconGeneral
BrandHirschmann
ModelMAR1040
CategorySwitch
LanguageEnglish

Related product manuals